  1. L

    L5-30 to 5-20 Question

    No they are not. I go through this every year with them. They were installed to meet the needs of one lighting company they used to rent from years ago.We will see what they decide.... Money is tight, so it may be the same story next year.
  2. L

    L5-30 to 5-20 Question

    Thank you all for the input! I thought I was right, but wanted to be sure.@BobHealey - Thank you for the Motion Labs link. I knew that if they didn't list it as a normal model I could definitely custom order one. Glad to see it's an off the self model.I'm very greatful for the vast amount of...
  3. L

    L5-30 to 5-20 Question

    Hi all,A venue recently asked me if I could simply build adapters (with no breakers, fuses, etc.) to convert from a L5-30 to 5-20 Edison. The L5-30s are currently permanently wired into an electrical panel with 50' of 10/3 SOOW and are protected with 30 amp breakers.I told the venue I could...