High school theatre fire in PA

Let me guess, the stage ceiling was at 49'-9"?

Is that a Smoke curtain frame at the opening? It looks framed and the bottom elevation would be about right.
 
Let me guess, the stage ceiling was at 49'-9"?

Is that a Smoke curtain frame at the opening? It looks framed and the bottom elevation would be about right.

Probably 35' give or take. Audience roof is the same height as the fly space, and from YouTube clips it looks like the proscenium is maybe 15' tall, max.

Probably not framing for a fire curtain you see there. Likely metal stud framing above the proscenium with the drywall scorched off it.

From the photos, looks like there is a concert grand on-stage and maybe choral/band risers, so I'm getting the impression the stage was not set up for a show and if they were working on a set for an upcoming show as the article says, that may have been taking place in the wings or in a scene shop.


1676319945122.png

1676319892705.png


1676320252672.png

1676320492571.png

1676321134344.png
 
  • Like
Reactions: Van
I have friend that was working on the production. He and the director where the last ones in the auditorium Saturday evening. This picture was taken Saturday afternoon.42867.jpeg
 
I should explain my comment. I have an issue with the extremely arbitrary <in my opinion> NFPA 80 codes surrounding Fire curtains. If the ceiling in your fly house is below 53' a fire curtain is not required to be installed many venues that do not have a fire curtain DO have a smoke curtain. If you aren't familiar a smoke curtain only deploys a 1/4 to 1/2 the height of the proscenium and is only intended to provide a catch for smoke so people can evacuate a given area. A lot of Architects/Designers will design Fly houses so the ceiling is at 49'-0" or so, this allows for thickness of roofing materials to keep everything under the 53' elevation restriction. This in turn, keeps down initial costs for new buildings. Fire curtains are expensive, must be maintained and tested regularly which means long-term maintenance costs. Because Theatre fires are rare now they aren't usually considered a priority. Getting off my soapbox now.

It appears, to me, that in this case a Fire curtain and adequate smoke hatches could have greatly reduced the damage to the rest of the Auditorium.
Thank god this happened at night and there were no injuries.
 
@Van, understandable, but a line has to be drawn somewhere and managing risk to property damage is a secondary goal to life safety. Wherever that line is drawn, at 50' or at 30', it will be viewed as arbitrary from one perspective or another. If you want to get into the weeds of what's possibly more valuable at this arbitrary line in the sand is that at 50', the envelope of the stage and auxiliary areas need to be beefed up in their partition ratings and the overall construction of these areas is enhanced to compartmentalize and slow the rate of spread.

Realistically, a fire curtain is most effective when someone is staffing the show and can pull the release before the fire and smoke spread, which serves the primary purpose of fire curtains to allow people to exit. If it's unoccupied and you have to wait for the fire to grow large enough for heat to accumulate on the downstage edge of the fly loft to trigger the solder links, you're probably already dealing with a substantial fire before the curtain deploys. Some, but not all fire curtains that are motorized may be tied in to the fire alarm system and if the particle detectors trigger could bring a fire curtain in an unoccupied building in sooner, but as one of my other consultants pointed out, the fire department will show up, make sure the building is evacuated, and as far as the stage is concerned they're going to let that puppy burn anyway and throw water on it from a healthy distance until the "crap stop's falling", at which point that 1-hr rating on the fire curtain is of marginal value if the fire is already roaring by the time they pull up. Also, if the only particle detectors in are in the ducts, they may not trigger if the AHU's are turned off after-hours -- which again would require 1) a motorized curtain that 2) is functional and maintained, and 3) is integrated with the fire alarm system.

As for smoke vents, they would likely have been required regardless as the stage appears to be larger than 1000sf, but I don't see any on the Google Earth images and I suspect it's an older building that was grandfathered in. In that vein, if it was non-sprinklered that could've played the most significant role. Though again, a small fire can become a large fire in the time it takes for enough heat to accumulate to trigger the sprinkler heads.

I'm seeing a lot of polystyrene in that set which brings with it toxic smoke, fast spreading of flames, and volatile chemicals used to texture the polystyrene where rags/towels/etc. covered in those chemicals can spontaneously combust if not disposed of properly in flammables bins that are promptly emptied each night. Not attempting to speculate on what happened, but hypothetically if a fire originated in a scene shop from a trash bin, it may well spread around the perimeter of the fly loft and into both the stagehouse and audience areas and bypass a fire curtain altogether.

At the end of the day, what's allowed to be grandfathered in on older buildings may have played a bigger role in the magnitude of this incident than the absence of a fire curtain may have -- and statistically speaking, fires in theaters are rare and fires where a fire curtain made any tangible difference are rarer yet. First and foremost, smoke vents and fire curtains exist to give people time to exit the building. Any protection of property is an added benefit but is not the primary reason for these requirements in code.

Could smoke vents and fire curtain have helped? Possibly, but chances are the building would still have been write-off as far as insurance was concerned.
 
@Van, understandable, but a line has to be drawn somewhere and managing risk to property damage is a secondary goal to life safety. Wherever that line is drawn, at 50' or at 30', it will be viewed as arbitrary from one perspective or another. If you want to get into the weeds of what's possibly more valuable at this arbitrary line in the sand is that at 50', the envelope of the stage and auxiliary areas need to be beefed up in their partition ratings and the overall construction of these areas is enhanced to compartmentalize and slow the rate of spread.

Realistically, a fire curtain is most effective when someone is staffing the show and can pull the release before the fire and smoke spread, which serves the primary purpose of fire curtains to allow people to exit. If it's unoccupied and you have to wait for the fire to grow large enough for heat to accumulate on the downstage edge of the fly loft to trigger the solder links, you're probably already dealing with a substantial fire before the curtain deploys. Some, but not all fire curtains that are motorized may be tied in to the fire alarm system and if the particle detectors trigger could bring a fire curtain in an unoccupied building in sooner, but as one of my other consultants pointed out, the fire department will show up, make sure the building is evacuated, and as far as the stage is concerned they're going to let that puppy burn anyway and throw water on it from a healthy distance until the "crap stop's falling", at which point that 1-hr rating on the fire curtain is of marginal value if the fire is already roaring by the time they pull up. Also, if the only particle detectors in are in the ducts, they may not trigger if the AHU's are turned off after-hours -- which again would require 1) a motorized curtain that 2) is functional and maintained, and 3) is integrated with the fire alarm system.

As for smoke vents, they would likely have been required regardless as the stage appears to be larger than 1000sf, but I don't see any on the Google Earth images and I suspect it's an older building that was grandfathered in. In that vein, if it was non-sprinklered that could've played the most significant role. Though again, a small fire can become a large fire in the time it takes for enough heat to accumulate to trigger the sprinkler heads.

I'm seeing a lot of polystyrene in that set which brings with it toxic smoke, fast spreading of flames, and volatile chemicals used to texture the polystyrene where rags/towels/etc. covered in those chemicals can spontaneously combust if not disposed of properly in flammables bins that are promptly emptied each night. Not attempting to speculate on what happened, but hypothetically if a fire originated in a scene shop from a trash bin, it may well spread around the perimeter of the fly loft and into both the stagehouse and audience areas and bypass a fire curtain altogether.

At the end of the day, what's allowed to be grandfathered in on older buildings may have played a bigger role in the magnitude of this incident than the absence of a fire curtain may have -- and statistically speaking, fires in theaters are rare and fires where a fire curtain made any tangible difference are rarer yet. First and foremost, smoke vents and fire curtains exist to give people time to exit the building. Any protection of property is an added benefit but is not the primary reason for these requirements in code.

Could smoke vents and fire curtain have helped? Possibly, but chances are the building would still have been write-off as far as insurance was concerned.
I want to say vents have been required since Iroquois burned, but I'm no expert. (Where I was had a cupola presumably for this since it was built in 1928. It was also sprinkled since construction. Note that we exceed 50' high).
 
As for smoke vents, they would likely have been required regardless as the stage appears to be larger than 1000sf, but I don't see any on the Google Earth images and I suspect it's an older building that was grandfathered in.

I was wondering about that, I'm guessing the aftermath photo with the sunlight streaming in is from where the roof was opened by the fire or FD? I've seen elementary school stages with stage ceilings at 20' with smoke hatches, is the square footage the determining factor for those for new construction?
 
I was wondering about that, I'm guessing the aftermath photo with the sunlight streaming in is from where the roof was opened by the fire or FD? I've seen elementary school stages with stage ceilings at 20' with smoke hatches, is the square footage the determining factor for those for new construction?
Yes, IBC states 1000sf as the threshold.

1676568490755.png

1676568531518.png

Some nuances apply, such as areas used for entertainment that may have primarily lighting and sound with a few masking leg curtains that do not meet an interpretation of overhead hanging curtains, which is why some black boxes over 1000sf may not require vents but a gymnacafetorium with border curtains might. I've seen those gray area projects that I considered stages (either based on what they were hanging or what they might want to hang down the road) go both ways where it comes down to local interpretation, usually at the behest of the life safety consultant and/or a third-party reviewer.

When I say "third-party reviewer", what I mean is a very common practice here in Florida is that in lieu of the jurisdiction providing plan review services, you can use a "private provider" who essentially reviews the project on largely-but-not-solely on behalf of the jurisdiction. This has the benefit of speeding up the permitting process and provide a continual review of plans throughout the design to mitigate surprises when the permit application is filed rather than dumping a set of plans in the City or County's hands and waiting for them to review 1000 sheets of drawings for a $100M high school all at once -- but in my opinion at times this private provider process may invite interpretative gymnastics which benefit the client whereas a local AHJ or fire marshal may take a more "belt and suspenders" approach.

As a side note, local interpretation is a funny thing at times. Not "haha" funny, but funny. For example, I had an outdoor amphitheater project a couple years ago with a canopy roof that was pitched at a strong angle (20° maybe?). The local fire marshal had a habit of requiring sprinklers for those structures and thus the architect and fire protection engineer spec'd a sprinkler system knowing this would be insisted upon by the AHJ.....BUT -- between the outdoor nature of the venue and the pitch of the canopy, it would take a meteor crashing into the venue to create enough heat to ever activate those sprinkler heads. There is no imaginable circumstance where they will ever achieve enough heat accumulation to activate, but even though it's not required by code, the AHJ gets what they want. Everyone on the design team was well aware it was a setting money on fire to bring a sprinkler main onto the site just for this but knew from past projects there was no escaping it.
 
Last edited:
....
As a side note, local interpretation is a funny thing at times. Not "haha" funny, but funny. For example, I had an outdoor amphitheater project a couple years ago with a canopy roof that was pitched at a strong angle (20° maybe?). The local fire marshal had a habit of requiring sprinklers for those structures and thus the architect and fire protection engineer spec'd a sprinkler system knowing this would be insisted upon by the AHJ.....BUT -- between the outdoor nature of the venue and the pitch of the canopy, it would take a meteor crashing into the venue to create enough heat to ever activate those sprinkler heads. There is no imaginable circumstance where they will ever achieve enough heat accumulation to activate, but even though it's not required by code, the AHJ gets what they want. Everyone on the design team was well aware it was a setting money on fire to bring a sprinkler main onto the site just for this but knew from past projects there was no escaping it.
I bet the AHJ had a Brother-in-law who was a plumber...;)
There is a jurisdiction near Portland where the local building review team has decided to give the DSA a run for their money. many of the comments received in regards to Fire & Structural code requirements have surpassed even the most out of touch DSA reviewers responses. (And that is coming from a safety freak like me. )
 
Even after all that the PA is still hanging. I don't normally like JBL VRX, but at least the rigging system is premium! -and it looks like you can see daylight through some of those boxes yet their still hanging.
 

Users who are viewing this thread

Back